Installation Manual03451 19/10/01Ventilation SystemsBRONZE MODELS90 H190 H®VB0023
103.0INSTALLATION (CONT’D)12"(305 mm)VO0004Cut 2 sections of the plastictube, about 12” (305 mm) longand attach them to each drainfitting.VO0005J
114.0INSTALLATION OF THE CONTROLS4.1 Electrical Connection to BRONZE Control4.2 Electrical Connection to Optional Controls4.3 Electrical Connection
125.0AIR FLOW BALANCINGVP0009VD0051WHAT YOU NEED TO BALANCE THE UNIT• A magnehelic gauge capable of measuring 0 to 0.5 inches in water (0 to 125 Pa) a
136.0OVERALL VERIFICATION6.1 3-Position SwitchThis procedure allows the installer to verify that all modes of operation are fully functional.During t
147.0MAINTENANCE• Warn the user of the necessity to rebalance the system following amajor house renovation or following the installation of any extra
159.0TROUBLESHOOTINGNote: Be sure to unplug and inspect the unit before proceeding with these steps. Start with point 1,then point 2 and so on.Start-
169.0TROUBLESHOOTINGProblems Possible causes You should try this5. The defrost cycle • Ice deposits may be hindering • Remove the ice.doesn't wo
21.0 TECHNICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31.1 Air Distribution (Normal Operation) . . . . . . . . . . .
31.0 TECHNICAL DATA* In a cold region, setup EXTENDED DEFROST by removing jumper JU1F on the circuit board.STALE AIR TO OUTSIDEFRESH AIR TO BUILDING1
VH000742.0 TYPICAL INSTALLATIONSVH0002VH0006See 3.4.1for detailsSee 3.4.2for detailsfigure 1figure 2ORfigure 4(Primarily for homes with radiant hot wa
53.0 INSTALLATIONINSPECT THE CONTENTS OF THE BOX• Inspect the exterior of the unit for shipping damage. Ensure that there isno damage to the door, doo
63.0 INSTALLATION (CONT’D)VI0003end branchesmain branch5”Ø70 cfm6”Ø 140 cfm140 cfmfigure 7figure 83.3 Calculating Duct SizeUse the table below to ens
73.0 INSTALLATION (CONT’D)3.4 Installing Ductwork and Registers3.4.1 Fully ducted system (as illustrated in Section 2.1)Stale air exhaust ductwork:•
Method 2: return side connection• Cut an opening into the furnacereturn duct at a minimum distance of 10 linear feetupstream where the furnacereturn d
93.0INSTALLATION (CONT’D)3.5 Connecting Duct to the UnitInsulated flexible duct:Use the following procedure for connecting the insulated flexible duc